Boiler alarms
Read what happened, prove the cause, and distinguish acknowledgment from recovery.
Alarm drill scope
These are separate fictional fault drills. Values, alarm delays, priorities, and reset rules are teaching examples, not universal OEM settings. “Correct simulated condition” records an assumed repair in this exercise; it does not command equipment or authorize a field reset.
CURRENT DRILL
Restricted boiler water flow
Resolve source alarms first and verify downstream symptoms separately. A hidden or acknowledged row does not establish equipment recovery.
| Priority / alarm | Equipment | Observed at | Condition | Acknowledgment | Latch | Event |
|---|---|---|---|---|---|---|
| Highboiler-low-flow | Boiler | — | ACTIVE | UNACKNOWLEDGED | Clear | #01 occurrence |
| Mediumboiler-strainer | Boiler | — | ACTIVE | UNACKNOWLEDGED | Clear | #01 occurrence |
EVENT JOURNAL
Keep the order of events.
Event numbers show action order. Times are local browser observations of the exercise. Records stay on this page until it reloads; no live alarm database is connected.
- #0 · —Scenario loaded: Restricted boiler water flow. Alarm conditions injected in the training workspace.
Read the alarm lifecycle.
Active condition
The fault condition remains true. Acknowledgment records an operator response and leaves the condition unchanged.
Returned to normal
The initiating condition is clear. Check independent proof and the process response before claiming recovery.
Latch / reset
A latching protection stays held after the condition clears. Its actual reset location, permissions, and restart procedure are equipment-specific.
PRIMARY SOURCE CONTEXT
Match the installed controller and approved sequence.
Pages 10–11 and 18–20: network point families and read/write distinctions; pages 35–37: BAS unit-operation scope. Available points and signal polarity vary by model; lab IDs are semantic aliases, not wire addresses.
Lochinvar CREST service manual, Rev X ↗Fault descriptions and local lockout/recovery context. The lab does not reproduce a specific controller's fault numbers or reset procedure.
Weil-McLain SVF 500/600 boiler manual — hydronic piping ↗Pages 19–26: example boiler/system circulation, separation, valves, expansion, air elimination, fill, and relief components. Original lab drawing is schematic and does not replace an approved installation design.
Weil-McLain SVF 500/600 boiler manual — sequence ↗Pages 84–87: standby, pre-purge, ignition, flame-proven modulation, post-purge, outdoor reset, and remote target context. Lab times are accelerated teaching values.
AERCO Edge controller communication manual ↗Integrator point-list examples include inlet/outlet/exhaust temperature, flame strength, firing rate, valve state, operating state, hours, and cycles. Signal units and scaling are device-specific.
AERCO Control System plant-management overview ↗Separates supervisory multi-boiler coordination and BAS monitoring from individual boiler operation. The lab represents a single active boiler branch.