The morning start produces no airflow
Air-handling unit · VFDs and motors · Foundation
Customer complaint
The building has entered occupied mode, but the AHU has not delivered air. Identify the missing link between the controller request and physical operation.
Equipment and operating sequence
Illustrative VAV AHU: all safety permissives are satisfied; a remote start must be accepted by the VFD. The allowed 30-second proof interval has elapsed.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Occupied request: true; effective fan start command: true for 90 seconds.
- VFD speed request: 60%; run feedback: false; output frequency: 0 Hz.
- Airflow proof: false; independent duct airflow: 0 cfm.
- VFD fault: none; all displayed points updated within 2 seconds.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.
Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Supply fan · case readings
- Supply fan start Command
- On
- Drive speed request Command
- 60 %
- Drive run Feedback
- False
- Drive output frequency Reading
- 0 Hz
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Supply fan start | Command · Supply fan | On | — | On | — | — | — |
| Drive speed request | Command · Supply fan | 60 | % | 60 | — | — | — |
| Drive run | Feedback · Supply fan | False | — | — | False | — | — |
| Drive output frequency | Reading · Supply fan | 0 | Hz | — | — | — | — |
| Duct airflow | Reading · Duct / zones | 0 | cfm | — | — | — | — |
Intake observations
- Occupied request: true; effective fan start command: true for 90 seconds.
- VFD speed request: 60%; run feedback: false; output frequency: 0 Hz.
- Airflow proof: false; independent duct airflow: 0 cfm.
- VFD fault: none; all displayed points updated within 2 seconds.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| AHU | VFD fault: none; all displayed points updated within 2 seconds. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.