Customer complaint

The building has entered occupied mode, but the AHU has not delivered air. Identify the missing link between the controller request and physical operation.

Equipment and operating sequence

Illustrative VAV AHU: all safety permissives are satisfied; a remote start must be accepted by the VFD. The allowed 30-second proof interval has elapsed.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Occupied request: true; effective fan start command: true for 90 seconds.
  • VFD speed request: 60%; run feedback: false; output frequency: 0 Hz.
  • Airflow proof: false; independent duct airflow: 0 cfm.
  • VFD fault: none; all displayed points updated within 2 seconds.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.

Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Supply fan · case readings

Supply fan start Command
On
Drive speed request Command
60 %
Drive run Feedback
False
Drive output frequency Reading
0 Hz

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Supply fan startCommand · Supply fanOn—On———
Drive speed requestCommand · Supply fan60%60———
Drive runFeedback · Supply fanFalse——False——
Drive output frequencyReading · Supply fan0Hz————
Duct airflowReading · Duct / zones0cfm————

Intake observations

  • Occupied request: true; effective fan start command: true for 90 seconds.
  • VFD speed request: 60%; run feedback: false; output frequency: 0 Hz.
  • Airflow proof: false; independent duct airflow: 0 cfm.
  • VFD fault: none; all displayed points updated within 2 seconds.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
AHUVFD fault: none; all displayed points updated within 2 seconds.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.