Customer complaint

Several zones are warm. The supply fan has reached its speed limit, but the AHU delivers less air than its recent commissioned baseline.

Equipment and operating sequence

Illustrative VAV AHU with a filter bank upstream of the fan. Reference readings are supplied at the same 8,000-cfm test airflow, eliminating airflow as the explanation for differing filter pressure drops.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Supply fan speed: 100%; duct static: 0.8 in. w.c.; active setpoint: 1.4 in. w.c.
  • Current total airflow: 8,000 cfm; recent full-load baseline: 11,000 cfm.
  • Several VAV dampers exceed 95% open; measured zone airflows are below their setpoints.
  • Filter differential pressure: 1.1 in. w.c.; no fan-drive fault.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.

Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Supply fan · case readings

Supply fan speed Reading
100 %

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Supply fan speedReading · Supply fan100%————
Duct static pressureReading · Duct / zones0.8in. w.c.————
Duct static targetSetpoint · Duct / zones1.4in. w.c.————
Filter pressure dropReading · Intake / mixing1.1in. w.c.————

Intake observations

  • Supply fan speed: 100%; duct static: 0.8 in. w.c.; active setpoint: 1.4 in. w.c.
  • Current total airflow: 8,000 cfm; recent full-load baseline: 11,000 cfm.
  • Several VAV dampers exceed 95% open; measured zone airflows are below their setpoints.
  • Filter differential pressure: 1.1 in. w.c.; no fan-drive fault.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
AHUFilter differential pressure: 1.1 in. w.c.; no fan-drive fault.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

EquipmentRecorded trend evidenceRecord source
AHUCurrent total airflow: 8,000 cfm; recent full-load baseline: 11,000 cfm.Intake record

Field mentor