The cooling valve is fully requested, but supply air is warm
Air-handling unit · Hydronic systems · Intermediate
Customer complaint
The AHU cannot reach its supply-air target. Determine whether the problem is temperature control, chilled-water availability, or the local coil circuit.
Equipment and operating sequence
Illustrative two-way chilled-water coil with a local strainer and an independently measured water flow. The exercise supplies commissioned performance references; valve travel alone does not establish water flow.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Entering coil air: 78°F; leaving air: 69°F; supply-air target: 55°F.
- Valve command: 100%; actuator feedback: 100%.
- Chilled water at branch inlet: 44°F; coil flow: 5 gpm versus a 25-gpm design reference.
- Other AHUs on the same plant receive adequate cooling; branch differential pressure is available.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.
Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Coils and valves · case readings
- Coil entering air Reading
- 78 °F
- Coil leaving air Reading
- 69 °F
- Cooling valve Command
- 100 %
- Actuator position Feedback
- 100 %
- Coil water flow Reading
- 5 gpm
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Coil entering air | Reading · Coils and valves | 78 | °F | — | — | — | — |
| Coil leaving air | Reading · Coils and valves | 69 | °F | — | — | — | — |
| Supply target | Setpoint · Duct / zones | 55 | °F | — | — | — | — |
| Cooling valve | Command · Coils and valves | 100 | % | 100 | — | — | — |
| Actuator position | Feedback · Coils and valves | 100 | % | — | 100 | — | — |
| Coil water flow | Reading · Coils and valves | 5 | gpm | — | — | — | — |
Intake observations
- Entering coil air: 78°F; leaving air: 69°F; supply-air target: 55°F.
- Valve command: 100%; actuator feedback: 100%.
- Chilled water at branch inlet: 44°F; coil flow: 5 gpm versus a 25-gpm design reference.
- Other AHUs on the same plant receive adequate cooling; branch differential pressure is available.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.