The occupied schedule is active, but the fan output remains off
Air-handling unit · Controls and communications · Advanced
Customer complaint
The schedule and automatic sequence request operation, yet the final command to the fan remains off. Find where the request loses authority.
Equipment and operating sequence
Illustrative commandable output: lower numbered active priority wins. Normal control writes at priority 16, and a non-safety maintenance override may write at priority 8. Life-safety and hardware interlocks are separate and satisfied.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Schedule: occupied; automatic sequence fan request: ON.
- Effective fan output: OFF; drive remote mode: enabled; drive fault: none.
- All required start permissives: satisfied; no output wiring fault indicated.
- The AHU ran normally before a maintenance visit; point timestamps are current.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.
Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.
Beckhoff BACnet documentation: Command prioritization ↗
Priority arrays, effective present value and relinquishing a command by writing NULL at its priority.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Duct / zones · case readings
- Occupied schedule Status
- Occupied
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Occupied schedule | Status · Duct / zones | Occupied | — | — | — | Occupied | — |
| Automatic fan request | Command · Supply fan | On | — | On | — | — | — |
| Effective fan output | Command · Supply fan | Off | — | Off | — | — | — |
| Drive remote mode | Status · Supply fan | Enabled | — | — | — | Enabled | — |
Intake observations
- Schedule: occupied; automatic sequence fan request: ON.
- Effective fan output: OFF; drive remote mode: enabled; drive fault: none.
- All required start permissives: satisfied; no output wiring fault indicated.
- The AHU ran normally before a maintenance visit; point timestamps are current.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| AHU | Effective fan output: OFF; drive remote mode: enabled; drive fault: none. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.