The office wing stays cold during morning warm-up
Air-handling unit · Hydronic systems · Intermediate
Customer complaint
The office manager feels air moving at the diffusers, but the wing is still cold. The plant operator reports that the heating pump is running. Find where heat delivery stops.
Equipment and operating sequence
AHU-01 serves this wing. During this occupied warm-up exercise its automatic supply air target is 75°F. The chilled-water plant is off for the season. The heating coil has a modulating control valve and separate manual isolation valves.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- At dispatch the office was 63°F, compared with its occupied target of 72°F.
- The supply air sensor read 61°F against a 75°F warm-up target. The supply fan had run for three minutes.
- The heating valve command and actuator feedback both read 100%.
- The heating pump showed run proof. Other areas on the same header were receiving heat.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Duct / zones · case readings
- Office temperature Reading
- 63 °F
- Supply air temperature Reading
- 61 °F
- Supply air target Setpoint
- 75 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Office temperature | Reading · Duct / zones | 63 | °F | — | — | — | — |
| Supply air temperature | Reading · Duct / zones | 61 | °F | — | — | — | — |
| Supply air target | Setpoint · Duct / zones | 75 | °F | — | — | — | — |
| Heating valve command | Command · Coils and valves | 100 | % | 100 | — | — | — |
| Heating actuator position | Feedback · Coils and valves | 100 | % | — | 100 | — | — |
| Plant pump run proof | Feedback · Coils and valves | On | — | — | On | — | — |
Intake observations
- At dispatch the office was 63°F, compared with its occupied target of 72°F.
- The supply air sensor read 61°F against a 75°F warm-up target. The supply fan had run for three minutes.
- The heating valve command and actuator feedback both read 100%.
- The heating pump showed run proof. Other areas on the same header were receiving heat.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.