System explorer
Work order BL-07

Boiler operates after occupied demand ends

Boiler · Controls and communications · Intermediate

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

The plant continues heating after the scheduled heating request ends. Determine which source still owns the enable command.

Equipment and operating sequence

Illustrative BACnet commandable heat-enable point: schedule logic writes at priority 15 and authorized temporary service commands at priority 8. No domestic-hot-water or freeze-protection demand is active.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • At 19:00, schedule demand changes to OFF, but effective heat enable remains ON.
  • The boiler receives the ON request and continues normal temperature control.
  • Supply remains near its 140°F target; local status shows no fault.
  • The normal schedule program output reads OFF.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.

Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.

Beckhoff BACnet documentation: Command prioritization ↗
Priority arrays, effective present value and relinquishing a command by writing NULL at its priority.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Boiler · case readings

Schedule demand Command
Off
Effective heat enable Command
On
Locally received request Feedback
On

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Schedule demandCommand · BoilerOff—Off———
Effective heat enableCommand · BoilerOn—On———
Locally received requestFeedback · BoilerOn——On——
Supply targetSetpoint · Supply header140°F————

Intake observations

  • At 19:00, schedule demand changes to OFF, but effective heat enable remains ON.
  • The boiler receives the ON request and continues normal temperature control.
  • Supply remains near its 140°F target; local status shows no fault.
  • The normal schedule program output reads OFF.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
BoilerSupply remains near its 140°F target; local status shows no fault.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

EquipmentRecorded trend evidenceRecord source
BoilerAt 19:00, schedule demand changes to OFF, but effective heat enable remains ON.Intake record