Dashboard reports cold water while local control is satisfied
Boiler · Controls and communications · Advanced
Customer complaint
The dashboard shows a persistent low-temperature alarm. Determine whether the plant or its displayed evidence needs correction.
Equipment and operating sequence
Illustrative local boiler control operates independently of a supervisory display cache. Low-temperature dashboard alarming uses the cached supply point; communications quality must be checked separately from the numeric value.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- At 10:20, dashboard supply reads 108°F against a 150°F target.
- The displayed point's last sample is 09:50, although its badge still says Good.
- Boiler local supply reads 150°F; its control loop is satisfied.
- Current independent system-supply reference reads 149°F and zones are comfortable.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.
Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Supply header · case readings
- Dashboard supply Reading
- 108 °F · 09:50 sample · Good flag
- Last dashboard sample Status
- 09:50
- Independent supply Reading
- 149 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Dashboard supply | Reading · Supply header | 108 | °F | — | — | 09:50 sample · Good flag | — |
| Last dashboard sample | Status · Supply header | 09:50 | — | — | — | 09:50 | — |
| Local boiler supply | Reading · Boiler | 150 | °F | — | — | — | — |
| Independent supply | Reading · Supply header | 149 | °F | — | — | — | — |
Intake observations
- At 10:20, dashboard supply reads 108°F against a 150°F target.
- The displayed point's last sample is 09:50, although its badge still says Good.
- Boiler local supply reads 150°F; its control loop is satisfied.
- Current independent system-supply reference reads 149°F and zones are comfortable.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| Boiler | At 10:20, dashboard supply reads 108°F against a 150°F target. | Intake record |
| Boiler | The displayed point's last sample is 09:50, although its badge still says Good. | Intake record |
| Boiler | Boiler local supply reads 150°F; its control loop is satisfied. | Intake record |