Work order BL-10

Dashboard reports cold water while local control is satisfied

Boiler · Controls and communications · Advanced

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

The dashboard shows a persistent low-temperature alarm. Determine whether the plant or its displayed evidence needs correction.

Equipment and operating sequence

Illustrative local boiler control operates independently of a supervisory display cache. Low-temperature dashboard alarming uses the cached supply point; communications quality must be checked separately from the numeric value.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • At 10:20, dashboard supply reads 108°F against a 150°F target.
  • The displayed point's last sample is 09:50, although its badge still says Good.
  • Boiler local supply reads 150°F; its control loop is satisfied.
  • Current independent system-supply reference reads 149°F and zones are comfortable.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.

Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Supply header · case readings

Dashboard supply Reading
108 °F · 09:50 sample · Good flag
Last dashboard sample Status
09:50
Independent supply Reading
149 °F

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Dashboard supplyReading · Supply header108°F——09:50 sample · Good flag—
Last dashboard sampleStatus · Supply header09:50———09:50—
Local boiler supplyReading · Boiler150°F————
Independent supplyReading · Supply header149°F————

Intake observations

  • At 10:20, dashboard supply reads 108°F against a 150°F target.
  • The displayed point's last sample is 09:50, although its badge still says Good.
  • Boiler local supply reads 150°F; its control loop is satisfied.
  • Current independent system-supply reference reads 149°F and zones are comfortable.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

EquipmentRecorded trend evidenceRecord source
BoilerAt 10:20, dashboard supply reads 108°F against a 150°F target.Intake record
BoilerThe displayed point's last sample is 09:50, although its badge still says Good.Intake record
BoilerBoiler local supply reads 150°F; its control loop is satisfied.Intake record

Field mentor