Work order CH-02

Condenser-side permissive never arrives

Chiller · Sequences of operation · Foundation

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

CHW flow is established, yet the machine remains unavailable to start. Determine why the condenser-water side cannot complete its sequence.

Equipment and operating sequence

Illustrative water-cooled chiller with a motorized CW isolation valve. The CW pump starts only after independent full-open proof; timeout is 60 seconds.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • 09:10: evaporator flow 480 gpm, valid; CHW permissive TRUE.
  • CW valve command OPEN for 90 seconds; open limit FALSE.
  • CW pump command OFF; condenser flow 0 gpm; no pump fault.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Evaporator · case readings

Evaporator flow Reading
480 gpm

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Evaporator flowReading · Evaporator480gpm————
Condenser valveCommand · Condenser systemOpen—Open———
Valve open limitFeedback · Condenser systemFalse——False——
Condenser flowReading · Condenser system0gpm————

Intake observations

  • 09:10: evaporator flow 480 gpm, valid; CHW permissive TRUE.
  • CW valve command OPEN for 90 seconds; open limit FALSE.
  • CW pump command OFF; condenser flow 0 gpm; no pump fault.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
ChillerCW pump command OFF; condenser flow 0 gpm; no pump fault.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.