Remote supply temperature stays above target
Chiller · Sensors and instrumentation · Intermediate
Customer complaint
The supervisor reports poor CHW supply temperature despite light compressor loading and satisfied zones. Decide whether cooling performance or measurement is wrong.
Equipment and operating sequence
The chiller controls from its own leaving-water sensor. A separate supervisory sensor is installed beside it in the same well-mixed leaving-water header.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- 13:15: supervisor CHWS 50°F; local leaving water 44°F; local target 44°F.
- Both readings are fresh; compressor load 38%; no active capacity limit.
- Zone temperatures are stable near their occupied targets.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Evaporator · case readings
- Supervisor CHWS Reading
- 50 °F
- Local leaving water Reading
- 44 °F
- Local target Setpoint
- 44 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Supervisor CHWS | Reading · Evaporator | 50 | °F | — | — | — | — |
| Local leaving water | Reading · Evaporator | 44 | °F | — | — | — | — |
| Local target | Setpoint · Evaporator | 44 | °F | — | — | — | — |
| Compressor load | Reading · Compressor | 38 | % | — | — | — | — |
Intake observations
- 13:15: supervisor CHWS 50°F; local leaving water 44°F; local target 44°F.
- Both readings are fresh; compressor load 38%; no active capacity limit.
- Zone temperatures are stable near their occupied targets.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.