Condensing temperature rises at comparable operating conditions

Chiller · Hydronic systems · Advanced

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

Compressor power is increasing although the tower delivers its usual water temperature. Separate tower performance from heat transfer inside the chiller.

Equipment and operating sequence

Illustrative flooded water-cooled chiller. Here condenser approach is saturated condensing temperature minus leaving condenser-water temperature; compare with this machine's clean baseline at matched load and flow.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • 14:40: entering CW 86°F; leaving CW 96°F; saturated condensing temperature 108°F; compressor power 140 kW.
  • Clean baseline at the same 200-ton cooling load and 577 gpm CW flow: 86°F entering, 95.5°F leaving, 98.5°F saturation, 100 kW.
  • Independent temperatures and pressure conversion agree; entering-air wet bulb is unchanged at 78°F.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Condenser system · case readings

Entering condenser water Reading
86 °F
Leaving condenser water Reading
96 °F
Condensing saturation Reading
108 °F

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Entering condenser waterReading · Condenser system86°F————
Leaving condenser waterReading · Condenser system96°F————
Condensing saturationReading · Condenser system108°F————
Compressor powerReading · Compressor140kW————

Intake observations

  • 14:40: entering CW 86°F; leaving CW 96°F; saturated condensing temperature 108°F; compressor power 140 kW.
  • Clean baseline at the same 200-ton cooling load and 577 gpm CW flow: 86°F entering, 95.5°F leaving, 98.5°F saturation, 100 kW.
  • Independent temperatures and pressure conversion agree; entering-air wet bulb is unchanged at 78°F.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

EquipmentRecorded trend evidenceRecord source
Chiller14:40: entering CW 86°F; leaving CW 96°F; saturated condensing temperature 108°F; compressor power 140 kW.Intake record
ChillerClean baseline at the same 200-ton cooling load and 577 gpm CW flow: 86°F entering, 95.5°F leaving, 98.5°F saturation, 100 kW.Intake record