The display looks satisfied, but the cooler is warm
Refrigeration system · Sensors and instrumentation · Foundation
Customer complaint
Find why the cooling call ends while independent box readings remain above target.
Equipment and operating sequence
R-134a medium-temperature cooler with TXV; room setpoint 35°F and documented 2°F differential. This is a static teaching snapshot; no product-safety decision is implied.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Controller room temperature: 35°F; independent center-box logger: 42°F at the same timestamp.
- Cooling demand: OFF; previous cooling cycles ended when the controller reached 35°F.
- Door closed; last defrost ended 90 minutes ago; both readings marked fresh.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.
Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Evaporator / box · case readings
- Controller room temperature Reading
- 35 °F
- Independent box logger Reading
- 42 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Controller room temperature | Reading · Evaporator / box | 35 | °F | — | — | — | — |
| Independent box logger | Reading · Evaporator / box | 42 | °F | — | — | — | — |
| Cooling demand | Command · Compressor | Off | — | Off | — | — | — |
Intake observations
- Controller room temperature: 35°F; independent center-box logger: 42°F at the same timestamp.
- Cooling demand: OFF; previous cooling cycles ended when the controller reached 35°F.
- Door closed; last defrost ended 90 minutes ago; both readings marked fresh.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| Refrigeration | Cooling demand: OFF; previous cooling cycles ended when the controller reached 35°F. | Intake record |
| Refrigeration | Door closed; last defrost ended 90 minutes ago; both readings marked fresh. | Intake record |