The freezer gets warmer every day
Refrigeration system · Sequences of operation · Foundation
Customer complaint
Use the event history to explain progressive loss of airflow and temperature control.
Equipment and operating sequence
Electric-defrost freezer; the approved site schedule contains four daily defrost starts. These are scenario-specific values. Evidence is supplied as snapshots, not a simulated melting process.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Box: 12°F against 0°F target; 48-hour trend shows progressively longer cooling calls.
- Evaporator face is heavily frosted; both fans rotate.
- Last completed defrost event: 72 hours ago.
- High-temperature alarm started after the second missed scheduled defrost window.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.
Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Evaporator / box · case readings
- Box temperature Reading
- 12 °F
- Box target Setpoint
- 0 °F
- Last completed defrost Status
- 72 h ago
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Box temperature | Reading · Evaporator / box | 12 | °F | — | — | — | — |
| Box target | Setpoint · Evaporator / box | 0 | °F | — | — | — | — |
| Last completed defrost | Status · Evaporator / box | 72 h ago | — | — | — | 72 h ago | — |
Intake observations
- Box: 12°F against 0°F target; 48-hour trend shows progressively longer cooling calls.
- Evaporator face is heavily frosted; both fans rotate.
- Last completed defrost event: 72 hours ago.
- High-temperature alarm started after the second missed scheduled defrost window.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| Refrigeration | High-temperature alarm started after the second missed scheduled defrost window. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| Refrigeration | Box: 12°F against 0°F target; 48-hour trend shows progressively longer cooling calls. | Intake record |
| Refrigeration | Last completed defrost event: 72 hours ago. | Intake record |
| Refrigeration | High-temperature alarm started after the second missed scheduled defrost window. | Intake record |