Work order RF-03

The freezer gets warmer every day

Refrigeration system · Sequences of operation · Foundation

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

Use the event history to explain progressive loss of airflow and temperature control.

Equipment and operating sequence

Electric-defrost freezer; the approved site schedule contains four daily defrost starts. These are scenario-specific values. Evidence is supplied as snapshots, not a simulated melting process.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Box: 12°F against 0°F target; 48-hour trend shows progressively longer cooling calls.
  • Evaporator face is heavily frosted; both fans rotate.
  • Last completed defrost event: 72 hours ago.
  • High-temperature alarm started after the second missed scheduled defrost window.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.

Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Evaporator / box · case readings

Box temperature Reading
12 °F
Box target Setpoint
0 °F
Last completed defrost Status
72 h ago

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Box temperatureReading · Evaporator / box12°F————
Box targetSetpoint · Evaporator / box0°F————
Last completed defrostStatus · Evaporator / box72 h ago———72 h ago—

Intake observations

  • Box: 12°F against 0°F target; 48-hour trend shows progressively longer cooling calls.
  • Evaporator face is heavily frosted; both fans rotate.
  • Last completed defrost event: 72 hours ago.
  • High-temperature alarm started after the second missed scheduled defrost window.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
RefrigerationHigh-temperature alarm started after the second missed scheduled defrost window.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

EquipmentRecorded trend evidenceRecord source
RefrigerationBox: 12°F against 0°F target; 48-hour trend shows progressively longer cooling calls.Intake record
RefrigerationLast completed defrost event: 72 hours ago.Intake record
RefrigerationHigh-temperature alarm started after the second missed scheduled defrost window.Intake record

Field mentor