The compressor restarts after the cooling call ends
Refrigeration system · Refrigeration · Intermediate
Customer complaint
Trace an off-cycle restart through a pumpdown sequence.
Equipment and operating sequence
TXV cooler with a normally closed liquid-line solenoid, receiver and automatic recycling pumpdown control. The thermostat closes the solenoid at satisfaction; a low-pressure control stops the compressor. Values are not universal switch settings.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Room demand: OFF; solenoid command and measured coil power: OFF.
- Compressor completes pumpdown, then restarts several times while room demand stays OFF.
- Suction pressure trend rises between restarts; no pressure values are required.
- Defrost is inactive; low-pressure switch events match the pressure trend.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.
Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Evaporator / box · case readings
- Room demand Status
- Off
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Room demand | Status · Evaporator / box | Off | — | — | — | Off | — |
| Solenoid | Command · Liquid line | Off | — | Off | — | — | — |
| Measured solenoid power | Feedback · Liquid line | Off | — | — | Off | — | — |
| Compressor | Status · Compressor | Repeating starts | — | — | — | Repeating starts | — |
Intake observations
- Room demand: OFF; solenoid command and measured coil power: OFF.
- Compressor completes pumpdown, then restarts several times while room demand stays OFF.
- Suction pressure trend rises between restarts; no pressure values are required.
- Defrost is inactive; low-pressure switch events match the pressure trend.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| Refrigeration | Compressor completes pumpdown, then restarts several times while room demand stays OFF. | Intake record |
| Refrigeration | Suction pressure trend rises between restarts; no pressure values are required. | Intake record |
| Refrigeration | Defrost is inactive; low-pressure switch events match the pressure trend. | Intake record |