Work order RF-06

The compressor restarts after the cooling call ends

Refrigeration system · Refrigeration · Intermediate

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

Trace an off-cycle restart through a pumpdown sequence.

Equipment and operating sequence

TXV cooler with a normally closed liquid-line solenoid, receiver and automatic recycling pumpdown control. The thermostat closes the solenoid at satisfaction; a low-pressure control stops the compressor. Values are not universal switch settings.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Room demand: OFF; solenoid command and measured coil power: OFF.
  • Compressor completes pumpdown, then restarts several times while room demand stays OFF.
  • Suction pressure trend rises between restarts; no pressure values are required.
  • Defrost is inactive; low-pressure switch events match the pressure trend.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.

Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Evaporator / box · case readings

Room demand Status
Off

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Room demandStatus · Evaporator / boxOff———Off—
SolenoidCommand · Liquid lineOff—Off———
Measured solenoid powerFeedback · Liquid lineOff——Off——
CompressorStatus · CompressorRepeating starts———Repeating starts—

Intake observations

  • Room demand: OFF; solenoid command and measured coil power: OFF.
  • Compressor completes pumpdown, then restarts several times while room demand stays OFF.
  • Suction pressure trend rises between restarts; no pressure values are required.
  • Defrost is inactive; low-pressure switch events match the pressure trend.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

EquipmentRecorded trend evidenceRecord source
RefrigerationCompressor completes pumpdown, then restarts several times while room demand stays OFF.Intake record
RefrigerationSuction pressure trend rises between restarts; no pressure values are required.Intake record
RefrigerationDefrost is inactive; low-pressure switch events match the pressure trend.Intake record

Field mentor