Refrigeration system · Refrigeration · Advanced
Customer complaint
Separate a valid electronic expansion-valve command from actual refrigerant feed.
Equipment and operating sequence
EEV-controlled R-134a cooler, with normal documented valve sizing and stable liquid supply. Displayed opening is commanded step position, not measured stem position. All checks reveal supplied service snapshots.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Box: 44°F; outlet saturation: 15°F; outlet tube: 40°F, giving 25°F superheat.
- EEV target superheat: 8°F for this authored case; commanded opening: 90%.
- Independent outlet temperature and pressure observations agree with controller inputs.
- EEV-inlet snapshot shows a 9°F subcooling margin, measured at the valve inlet.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.
Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Evaporator / box · case readings
- Evaporator saturation Reading
- 15 °F
- Outlet tube Reading
- 40 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Evaporator saturation | Reading · Evaporator / box | 15 | °F | — | — | — | — |
| Outlet tube | Reading · Evaporator / box | 40 | °F | — | — | — | — |
| EEV target superheat | Setpoint · Liquid line | 8 | °F | — | — | — | — |
| EEV opening | Command · Liquid line | 90 | % | 90 | — | — | — |
Intake observations
- Box: 44°F; outlet saturation: 15°F; outlet tube: 40°F, giving 25°F superheat.
- EEV target superheat: 8°F for this authored case; commanded opening: 90%.
- Independent outlet temperature and pressure observations agree with controller inputs.
- EEV-inlet snapshot shows a 9°F subcooling margin, measured at the valve inlet.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.