Level 2 · Practical exam

The pressure reading and the occupied zone

Trace one signal through its input, conversion and displayed value. Then test whether a commanded device delivers the requested physical change.

Practical evidence

Your verified practical records are attached below. The signed report and an independent knowledge pass are both required. The simulator verifies the practical checks. Your written conclusion is retained for review.

Practical outstanding.

Independent transfer assessment

Pass at 80%. Every safety item must also pass.

1. The duct reference is 125 Pa and the transmitter gives 12 mA on that range. The graphic reads 188 Pa. Which boundary should you check next?
2. A 2–10 V speed reference maps linearly to 0–60 Hz. What frequency is requested at 8 V?
3. A transmitter spans 0–250 Pa over 4–20 mA. What pressure does 8 mA represent?
4. A thermistor circuit needs a resistance check. Which action preserves the meter and controller? · Required for safety
5. A damper shows 100% command and 100% actuator feedback. Which observation tests the delivery to this room?