Level 4 · Practical exam

Turn over the occupied air system

Resolve independent delivery and data-quality dispatches, then submit the commissioning project's as-found, correction and restoration records.

Practical evidence

Your verified practical records are attached below. The signed report and an independent knowledge pass are both required. The simulator verifies the practical checks. Your written conclusion is retained for review.

Practical outstanding.

Independent transfer assessment

Pass at 80%. Every safety item must also pass.

1. One controller is visible at the local panel but several supervisory points show the same old timestamp. Which test narrows the communication boundary?
2. Which handoff entry supports final acceptance? · Required for safety
3. A valve passes endpoint motion. Under steady demand, the coil has no measurable increase in leaving-air temperature. What remains to prove?
4. A fictional gateway map labels a signed room temperature as raw tenths of a degree Celsius. The decoded signed value is −36. What temperature should appear?
5. A pressure sensor agrees at zero but increasingly underreads a reference at midrange and full scale. What candidate best fits?