Common BACnet objects and properties
Identify a point by device, object type and instance, then inspect the property used by the graphic.
Common objects in a building controller
| Object type | Typical use and verification |
|---|---|
| Device | Identifies a BACnet device and exposes identifying information. Record the device instance and actual network location. |
| Analog Input (AI) | A measured analog quantity. Compare Present_Value, Units, available status flags and update time against the field condition. |
| Analog Output (AO) | An analog demand, such as speed. Inspect effective Present_Value and applicable priority entries, then verify physical response. |
| Analog Value (AV) | A numeric software value such as a setpoint. Find the producing logic or remote writer. |
| Binary Input (BI) | Two-state observation, such as a run contact. Verify inactive/active text and physical contact state. |
| Binary Output / Value (BO / BV) | Two-state command or software flag. Establish the effective state, writer and relevant interlocks. |
| Multi-state Value (MSV) | Enumerated mode. Read the configured state text before interpreting an integer. |
| Schedule / Calendar | Time-based values and exception dates. Inspect device time, weekly entries, exceptions and write priority. |
| Trend Log | A configured record of a property over time. Confirm object binding, logging interval or trigger, units and retention. |
Field example
Device 416, Analog Input 3 at 68°F can coexist with Device 417, Analog Input 3 at 74°F. The AI number alone cannot identify which room the workstation is displaying.
Procedure
- Match the manufacturer’s exact model/version and its protocol implementation conformance statement (PICS).
- Record device instance, object type, object instance and property, plus source timestamp.
- For a commandable property, check the highest effective priority and release temporary commands at their original priority.