Networks
Network troubleshooting guide
Localize an unavailable or stale value using the network riser, device identity, time and health of neighboring devices.
Observations that separate failure scopes
| Observation | Next evidence |
|---|---|
| One point stale, other points on that controller fresh | Check the exact object or register binding, polling or change reporting, quality and source timestamp. |
| One field controller missing from an otherwise healthy trunk | Check its local power and status, documented addressing, configuration changes and last successful communication. |
| Every downstream MS/TP controller missing | Compare router status, a known local controller and the affected segment against the as-built bus. Verify physical trunk continuity and configured baud rate under authorized procedures. |
| Intermittent MS/TP errors after a device addition | Compare MAC addresses on that segment, bus topology and documented termination/bias provisions. Match the manufacturer’s terminal designations and installation instructions. |
| IP controller locally reachable but supervisory values stale | Compare IP address, subnet, expected path and BACnet network settings with the approved inventory. Local connectivity alone does not validate object bindings. |
| Modbus device responds but pressure is implausible | Verify serial settings or TCP unit mapping, function and register, address-base convention, signedness, byte/word order and numeric scaling against its published register map. |
Field example
Three east-wing controllers share one router. Their supervisory values stopped at 15:23 while points behind a second router remain fresh. Observe local controller operation and router/trunk health before readdressing any individual controller.
Practice and related lessons
Technical references
- Johnson Controls · MS/TP communications bus technical bulletin
- BACnet International · BACnet glossary
- Modbus Organization · Application, serial line and TCP specifications
- Siemens · Discovering a BACnet network
- Johnson Controls · BACnet/IP broadcast routing behavior
- BACnet Committee · Objects, Properties and Services
- DOE FEMP · Commissioning for Federal Facilities