Module examinationPass at 80%. 1. Which pair uniquely locates this process object on the simulated BACnet internetwork?Controller device instance and object identifierMechanical room and displayed temperaturePoint nickname and units2. A 30% P8 command is released. P12 holds 60% and P16 holds 25%. Which output wins?Answer (%)3. A controls change appears to resolve the complaint. Which handoff lets a second technician reproduce and reverse it?An image of the green equipment iconA new file named final with its old version discardedBefore/after logic versions, affected point bindings, authorization, test evidence and rollback conditions4. Which statement best describes the result to the building manager?The work order passed because the alarm was acknowledged.Occupied airflow returned and held for five minutes. The next automatic morning start is scheduled for follow-up.Unit fixed permanently.5. 08:21 to 08:26 is how many minutes of observed operation?Answer (min)6. The points list and latest mechanical schedule specify different sensor locations. What belongs in the discrepancy record?A silent graphic editBoth revision identifiers, observed field location and the decision ownerOnly the older location7. Which service handoff best supports authorized future recovery?An emailed shared passwordA screenshot of the successful download aloneA verified backup revision, change log, post-change evidence and rollback owner8. A network riser and verified switch inventory disagree about one controller connection. What belongs in the report?A final redraw based solely on the riserThe disagreement, timestamped observations, confidence limits and the authorized verification neededAn immediate change to the live network to see which device disappearsSubmit assessmentApply this material in Unit 2Follow a point from the field to the graphicApply this material in Unit 11Work an intermittent call and hand it offReturn to Learning Center