Module examinationPass at 80%. 1. Cooling-tower water enters at 94°F and leaves at 83°F. Entering air wet bulb is 76°F. Calculate approach.Answer (°F)2. Chilled-water flow is proven and condenser flow reads zero. Which next check follows the heat rejection path?Increase the lead stage timerLower the chilled-water targetTrace condenser pump status, isolation valves and independent condenser flow3. At 100% damper position a VAV box delivers only half its flow target. Which check is most discriminating?Raise zone temperatureRequest heat-pump reversalCheck independent inlet pressure and verify flow pickup4. What observation establishes that a heat pump is delivering heat to its indoor airstream?An available heat-mode iconCompressor status aloneSustained leaving-air temperature above entering-air temperature under airflow, with auxiliary heat accounted for5. Plain water flows at 80 gpm through a heating plant with an 8°F supply-to-return difference. Estimate transferred heat.Answer (Btu/h)6. A water coil receives 14 gpm. Its entering and leaving water temperatures are 152°F and 139°F. Estimate heat released using 500 × gpm × ΔT.Answer (Btu/h)7. With a fan request on, motor proof on and zero measured airflow, which check best separates drive operation from air delivery?Lower the occupied targetShorten compressor delayCompare wheel rotation, drive transmission and an independent duct reading8. An RTU blower is proven and outdoor-air cooling is insufficient. A compressor command is on, compressor proof stays off and discharge temperature stays near mixed air. Where should diagnosis continue?At the DX permissives and independent compressor stateAt the condenser fan blade countAt the occupied schedule only9. An unoccupied unit starts during a cold night. Which information should you compare before calling it a schedule fault?Fan manufacturer's serial numberYesterday's occupied fan speedCurrent setback target and zone temperatureSubmit assessmentApply this material in Unit 4Follow the sequence of operationApply this material in Unit 6Diagnose airside deliveryApply this material in Unit 7Diagnose hydronic deliveryReturn to Learning Center