Module examinationPass at 80%. 1. Which pair shares a local IPv4 subnet when both have a /24 mask?192.0.2.14 and 192.0.3.14192.0.2.14 and 198.51.100.14192.0.2.14 and 192.0.2.832. The gateway's BACnet object just updated but its serial meter sample is 40 minutes old. Which timestamp determines the age of the measurement?The meter's last successful sample timeThe gateway's last reboot timeThe time the operator opened the graphic3. A documented 16-bit register is a signed integer in tenths of a degree. A raw positive reading of 237 represents what temperature?Answer (°C)4. A controller regulates its room locally while its supervisor trend is stale. What has the room response established?The temperature sensor is perfectly calibratedEvery network hop is healthySome local sensing and control continue independently5. A register holds 317 counts with 0.1 kW per count. What should the supervisory trend show?Answer (kW)6. Two controllers have unique device instances but the same MS/TP MAC on one segment. The routed IP side stays healthy. Which simulated correction addresses the conflict?Assign unique segment MAC addresses and check fresh responses from both devicesAssign the same device instance to bothRescale their temperature objects7. The IP address is 192.0.2.70 with a /26 mask. Which peer lies in the same IPv4 subnet?192.0.2.160192.0.2.30192.0.2.1108. Two different devices both expose Analog Input 1. What additional identifier distinguishes those objects in the workstation binding?The device instanceThe sensor's display precisionThe same units9. An installer enables end-of-line resistors at every controller. Which issue can this introduce?A new global BACnet device instanceAutomatic correction of duplicate addressesExcess electrical loading of the segmentSubmit assessmentApply this material in Unit 9Diagnose network and data-quality faultsReturn to Learning Center