Sequence study

RTU-01 / Rooftop mixed-air section

System graphicRTU-01
RTU-01 packaged rooftop unit, service-side cutawayOutdoor air enters the left hood and mixes with return air rising from the curb. Air crosses a shallow framed pleated panel filter and the DX evaporator coil, enters the centrifugal supply blower and discharges down through the roof. A bulkhead separates the air handler from the compressor, outdoor condenser coil and two top-discharge propeller fans.Outdoor air hoodMixing sectionSupply blowerTop-discharge condenser fansReturn air ↑Pleated filterEvaporator coilSupply air ↓CompressorCondenser coil
Outdoor and return air cross the pleated filter and evaporator before the blower delivers supply air down through the curb. The right-hand condenser bay discharges upward.

The mixed-air estimate weights outdoor and return temperatures by the outdoor-air fraction. The exercise assumes steady, sensible mixing and excludes fan and coil heat. Outdoor-air fraction is an input separate from damper position.

Sequence documentation

These values belong to this isolated training exercise. Changing an input recalculates the displayed result.

Economizers and outdoor-air evidence →Johnson Controls · Packaged rooftop equipment guide ↗