Skip to workspace
BAS Bridge
System explorer

Refrigeration system

REF-01 Refrigeration circuit

Cooling snapshot

Operating sequence

Selectable snapshots: conventional pump-down + electric defrost. No physics simulation or live equipment.

REF-01 · SELECTABLE TEACHING SNAPSHOTOne circuit. Separate equipment states.
Cooling
Select equipment to inspect
Conventional refrigeration circuit: CoolingCompressor running; liquid solenoid open; evaporator fan running; electric heater off. Condenser fan operation is not specified. Arrows illustrate the conventional refrigerant circuit while refrigeration is enabled. Colors identify schematic path types, not measured refrigerant temperatures or pressures.FUNCTIONAL CIRCUIT + EQUIPMENT CUTAWAYSILLUSTRATIVE ARRANGEMENT · NO LIVE DATACONDENSERCD-01Fan: not specified in snapshotRECEIVERLIQUIDRECEIVERSOLENOIDOPENMETERINGDEVICECP-01COMPRESSORRUNNINGDischarge pathSuction returnEV-01EVAPORATORFan: runningHeater: off

The full circuit stays in view. Use the equipment buttons for readable observations, or open component detail.

Compressor RunningLiquid feed OpenEvaporator fan RunningHeater OffCondenser fan Not specified

Discharge Liquid Evaporator / suction

Arrows illustrate the conventional refrigerant circuit while refrigeration is enabled. Path colors are schematic; temperatures, pressures and receiver level are not measured. Unspecified commands follow the selected teaching snapshot.

SELECTED STATE 1

Cooling

A valid cooling call and cleared permissions allow refrigeration.

What ends this state?

Room demand becomes satisfied, or an approved defrost request begins the next sequence.

Liquid feed: OPENCompressor: RUNNINGEvaporator fan: RUNNINGHeaters: OFF
Snapshot scope & arrangement

Each case pass requires the supported diagnosis, the two specified evidence relationships and the best next action. The example combines conventional solenoid pump-down with electric-defrost concepts. Actual fan, valve, pressure-control and restart logic varies by equipment. A defrost request takes its own branch from normal operation; standby is shown to explain satisfied demand. Equipment cutaways are joined by a simplified functional circuit, not an installation layout. The metering-device detail is illustrative, not model-specific valve or sensing-bulb installation guidance. No pressures, temperatures, receiver levels or unspecified equipment states are calculated.

0 / 5 cases passed · Refrigeration lessons

Field case assessments

Case briefCompressor still running after the call ends

Fictional training call · Restaurant walk-in cooler using conventional liquid-solenoid pump-down control

Customer report

“The room thermostat says it is satisfied, but I can still hear the compressor. Is it stuck on?”

The service request arrives during a short transition on a system whose documented sequence includes pump-down.

Still running after satisfaction

This fictional system uses a documented conventional liquid-solenoid pump-down circuit. Observe the transition before deciding that the compressor failed to stop.

Select the solenoid command and the suction-pressure response that support pump-down (two items)
Best supported conclusion
Best next action
0/2 evidence items selected

MANUFACTURER CONTEXT

Learn the logic. Match the actual equipment.

No live controls, bypasses or equipment settings are provided. Use the exact equipment literature and approved isolation, protection and restoration procedures for field work.