The displayed duct pressure stays low as the building gets noisy
Air-handling unit · Sensors and instrumentation · Intermediate
Customer complaint
The supply fan accelerates even though several zones have excessive diffuser noise. Identify the pressure value governing the fan and validate it.
Equipment and operating sequence
Illustrative VAV AHU: the static-pressure controller uses a differential transmitter with its high port connected to the duct tap and low port referenced as documented. The existing independent high-static limit remains functional.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Controller static: 0.1 in. w.c.; active target: 1.2 in. w.c.
- Fan speed: 95%; most VAV dampers: 15–25% open.
- Several zones meet temperature and airflow targets but report noise.
- Static value is fresh, not stale; high-static shutdown has not occurred.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.
Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Duct / zones · case readings
- Controller duct static Reading
- 0.1 in. w.c.
- Static target Setpoint
- 1.2 in. w.c.
- VAV damper positions Feedback
- 15–25 %
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Controller duct static | Reading · Duct / zones | 0.1 | in. w.c. | — | — | — | — |
| Static target | Setpoint · Duct / zones | 1.2 | in. w.c. | — | — | — | — |
| Fan speed | Reading · Supply fan | 95 | % | — | — | — | — |
| VAV damper positions | Feedback · Duct / zones | 15–25 | % | — | 15–25 | — | — |
Intake observations
- Controller static: 0.1 in. w.c.; active target: 1.2 in. w.c.
- Fan speed: 95%; most VAV dampers: 15–25% open.
- Several zones meet temperature and airflow targets but report noise.
- Static value is fresh, not stale; high-static shutdown has not occurred.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| AHU | Static value is fresh, not stale; high-static shutdown has not occurred. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.