What you’ll learn
- Scale 0–10 VDC, 2–10 VDC and 4–20 mA using their endpoints.
- Separate a signal-range mismatch from an actual pressure change.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.Write down four endpoints
Identify the electrical low and high values, then the process low and high values. Fraction of span equals (signal minus electrical low) divided by electrical span. Multiply this fraction by the process span and add the process low. A 12 mA input is halfway through a 4–20 mA range. An output commanding 50% sends 5 V on a 0–10 V output and 6 V on a 2–10 V output. A measured value outside range needs investigation even when software clamps it to a plausible display.
Choose the appropriate measurement
Read a voltage signal between its signal and designated common. A current loop carries the same series current through its components. For a known installed 250 Ω receiver, a 12 mA signal drops 3 V across that receiver. Use the documented test provision or suitable process clamp where available. Placing a current-range meter across a supply can create a short. Confirm source, receiver input type, polarity and power arrangement before interpreting a live zero or loss of signal.
- Actual duct pressure
- Transmitter range
- 4–20 mA output
- AI mode and scaling
- Displayed pressure
Normal operation
Example training conditions
- A linear transmitter maps 0–100 psi to 4–20 mA. At a 50 psi reference the input receives 12 mA and displays 50 psi.
- The live zero is 4 mA. Subtract it before dividing the measured signal by the 16 mA span.
Worked service example
A pressure trend appears consistently high after a transmitter replacement.
Recorded field evidence · training example
- Transmitter label 0–2 in. w.c. = 4–20 mA.
- Loop current 12 mA. Manometer 1.00 in. w.c.
- Operator display 1.50 in. w.c. AI configured 0–3 in. w.c.
The transmitter and reference agree at the midpoint. The AI engineering span turns that correct current into 1.50. Verify both configured endpoints against the approved range and test another point before accepting the correction.
Field procedure
- Record electrical signal type, range, units and reference common or loop path.
- Convert the observed signal manually before reading the software scaling.
- Check both endpoints or two separated reference values to distinguish an offset from an incorrect span.
Hands-on exercise
Use the converter at low, midpoint and high signal. Repeat the midpoint conversion with a different engineering span.
Analog signal converter
Set a 0–100 psi, 4–20 mA transmitter to the signal that represents 75 psi.
Unit 2 service call
The pressure on the graphic disagrees with the field transmitter.
Locate the first disagreement between the field signal, controller conversion and displayed value. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
Check a duct static pressure transmitter
Compare the transmitter indication and reference manometer. Decide whether the pressure or its representation requires correction.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Always subtract the live zero and include the engineering offset.
- Prove both scaling and the physical quantity with independent readings.