Analog signal conversion table

Look up common fractions of a linear 0–10 V, 2–10 V or 4–20 mA span.

Linear input and output checkpoints

Linear input and output checkpoints
Span0–10 VDC2–10 VDC4–20 mA
0%0 V2 V4 mA
25%2.5 V4 V8 mA
50%5 V6 V12 mA
75%7.5 V8 V16 mA
100%10 V10 V20 mA

Field example

A 0–5 in. w.c. transmitter produces 16 mA. It is at 75% span, or 3.75 in. w.c. On a signed −1 to +1 in. w.c. range, the same current represents +0.50 in. w.c.

Procedure

  1. Check input mode and the transmitter’s physical endpoints.
  2. Convert measured electrical value to a span fraction. Apply engineering span and offset.
  3. Test at two separated conditions. Confirm whether square-root extraction or custom scaling changes the mapping.