Level 2 · Sensors and transmitters

Verify temperature, humidity and CO₂ at the sensing point

22 minutes · Intermediate

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Distinguish sampling-location errors from drift or incorrect scaling.
  • Choose conditions for a repeatable reference comparison.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

Two accurate instruments can disagree

A wall sensor over a cable opening can sample air from the wall cavity. A mixed-air probe downstream of a poorly mixed damper can sit in a cold streak. A short pipe probe may miss the flowing stream. Match the independent instrument to the complaint, place it beside the installed sensing element and wait for both to stabilize. Repeat elsewhere in the occupied zone to separate a site representation problem from an instrument error.

Temperature affects relative humidity

Relative humidity (RH) compares water-vapor pressure with the value at the current temperature. Heating a sample at constant moisture content generally lowers its RH. Place the reference and installed probes in the same air and compare their temperatures as well as RH. A cool probe near condensation or a warm transmitter enclosure can the comparison.

Evaluate the CO₂ trend over occupancy

A non-dispersive infrared CO₂ sensor estimates gas concentration from infrared absorption. A sensor near an occupant’s breath or supply diffuser may give a poor representation of the room. Check ppm range and airflow pattern. Some sensors use a baseline correction that assumes periodic exposure to a low concentration. Verify the specific sensor’s calibration method before applying that assumption in a continuously occupied space.

Distinguish drift from a placement error

Sensor drift develops as its response changes over time. A sensor in sunlight can also disagree with a room thermometer while measuring its own local conditions correctly. Put a suitable reference next to the sensing element, allow both to stabilize and record the differences at several conditions. Repeat after the suspected draft or radiant load changes. Compare instrument uncertainty with the project tolerance before changing an offset.

Local comparison before a calibration adjustment
  1. Identify element and location
  2. Co-locate reference
  3. Allow settling
  4. Compare raw signal
  5. Check BAS scaling
  6. Repeat at second condition

Normal operation

Example training conditions

  • In a well-mixed occupied room the wall sensor reads 72.4°F and a stabilized reference beside it reads 72.6°F. A nearby air sample reads 45% RH.
  • Compare each quantity with a reference for the same quantity. Record sensor locations, instrument uncertainty and stabilization time.

Worked service example

An office VAV box overcools its zone while the room graphic reports 77°F.

Recorded field evidence · training example

  • Wall sensor and independent probe at its inlet both read 77°F.
  • At desk height in the occupied area the reference reads 71°F.
  • Warm air enters through the sensor wiring opening.

Agreement at the sensor narrows the discrepancy to sampling location or air leakage. A software offset could mask today’s draft and create a new error when the plenum temperature changes.

Field procedure

  1. Document occupancy, sensor location, airflow exposure and response time.
  2. Compare a co-located reference at stable conditions, then check a representative occupied location.
  3. Check the installed range, curve and calibration instructions before changing any offset.

Hands-on exercise

Vary the simulated element temperature. Predict whether its resistance rises or falls, then compare the displayed curve with the installed element type.

Resistance temperature sensor

This example uses a 10 kΩ NTC at 25°C and a 3,950 K beta coefficient. Use the installed sensor’s curve for a field comparison.

−10°C60°C
Resistance (kΩ)
Isolated meter · 12535 Ω

Compare the connected and open readings. Leave the circuit open at 25°C and record the resistance you would expect after reconnecting a healthy sensor.

Unit 3 service call

The damper shows full travel. The room still has very little air.

Separate the electrical indication, physical movement and measured delivery. Bring back the source, reading and time of your strongest observation.

Open case simulator

Knowledge check

Pass at 80%.

1. A wall sensor and its adjacent reference both read 78°F. A second room location reads 72°F. Which test is most useful next?
2. A stabilized reference reads 71.2°F next to a room probe reporting 73.0°F. What is the signed probe-minus-reference difference?
3. A return-air RH probe reads higher than a warmer reference brought from a service truck. Which observation makes the comparison meaningful?
4. A CO₂ instrument near an occupant's face reads much higher than the wall sensor elsewhere in the room. Which repeat supports a sensor comparison?
5. A duct transmitter and a calibrated local probe rise together while a BAS point stays flat. Which check most directly separates scaling from stale reporting?

Field takeaways

  • Match instruments in time, place and temperature.
  • Use calibration adjustments only after ruling out placement and configuration errors.