Measurements
Sensor troubleshooting guide
Locate disagreement among the sampled condition, sensor element, transmitter, controller input and displayed units.
Common measurement patterns
| Pattern | A discriminating check |
|---|---|
| Constant offset at two stable points | Co-locate a calibrated reference. Check placement, documented offset and wiring error before changing calibration. |
| Agreement at low end, growing error at high end | Inspect input/transmitter endpoints and exact element curve. Compare at another well-separated reference value. |
| RTD or thermistor jumps when the cable moves | Under verified isolation compare element and cable resistance separately. Check leads and terminations against the sensor documentation. |
| Duct static stays near zero while airflow changes | Compare a manometer at the same taps. Inspect pinched or leaking lines, port assignment, range and displayed resolution. |
| CO₂ stays unusually low in a continuously occupied room | Compare an independent ppm reading at the same location, then check range, sampling location and how the specific sensor establishes its baseline. |
| Relative humidity disagrees at two locations | Bring both sensors into the same air and compare temperature during stabilization. Temperature differences can explain a change in RH. |
Field example
At 12 mA, a pressure transmitter and local gauge indicate 1.0 in. w.c. The controller shows 1.5. A correct midpoint electrical signal and independent reference move the investigation toward the input configuration.
Practice and related lessons
Technical references
- Belimo · Resistance characteristics of passive temperature sensors
- Belimo · CO₂ sensing and automatic baseline correction
- Siemens · Configuring controller I/O
- Fluke · Measuring a 4–20 mA loop signal
- Fluke · Measuring resistance with a digital multimeter
- BACnet Committee · Objects, Properties and Services
- DOE FEMP · Commissioning for Federal Facilities