What you’ll learn
- Explain when an ohms reading represents one component.
- Use a resistance table and an isolation sequence to discriminate an open circuit from a scaling error.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.An ohmmeter supplies its own test current
A meter calculates resistance from a small internal test current. External voltage invalidates that test and can damage the instrument. Parallel return paths can make a disconnected winding appear continuous when measured in circuit. In the virtual trainer open the disconnect, apply the lock and tag, verify zero across X1 and X2 in AC voltage mode, then lift the coil test link. A field procedure must account for all energy sources, suitable test equipment and verification under the site’s energy-control program.
Compare like elements
A passive temperature input uses a resistance-to-temperature curve. A platinum RTD normally increases in resistance as temperature rises. A negative-temperature-coefficient thermistor normally decreases. Different 10 kΩ thermistors can agree at 25°C and diverge away from that point. Identify the element model, isolate it from the input as required and compare with a reference at its sensing tip. Then compare the resistance at the field end and the disconnected controller end to locate a wiring discrepancy.
- Document live symptom
- Isolate and secure circuit
- Verify absence of voltage
- Lift specified test link
- Measure component
- Restore and prove operation
Normal operation
Example training conditions
- On the isolated and verified training board, a disconnected example winding reads 48 Ω on its resistance range. Shorted test leads read near 0 Ω and separated leads indicate an open circuit.
- The winding's specified DC resistance and its AC operating current describe different tests.
Worked service example
A supply fan receives a start but the relay never pulls in.
Recorded field evidence · training example
- Virtual coil measured 23.99 VAC during the call.
- Verified isolated X1–X2 0.00 VAC. Test link lifted.
- A1–X2 in resistance mode reads OL.
An in-range voltage and an open isolated winding support a broken coil circuit. A mechanically jammed relay with an intact winding would still show finite isolated resistance. On a physical meter OL can also indicate resistance beyond its range. Verify the setup and expected range.
Field procedure
- Take and record the energized observation only on the virtual test board.
- Verify isolation using the required voltage mode and terminals. Lift the correct link.
- Test the isolated component against its expected resistance or curve. Reconnect and verify operation after any simulated repair.
Hands-on exercise
Try a resistance measurement in an energized virtual circuit. Establish the required isolated condition and compare the meter response.
Trace the fan relay circuit
Record the live control source and relay coil voltages. Open and lock the simulated disconnect, prove the secondary dead, lift the test link and record the isolated coil resistance. Compare the three readings to locate the failed component.
Scroll the diagram sideways to reach all six terminals, or use the lead selectors.
F1 supplies the controller and the series start path. K1’s normally open contact grants the drive run permission. The enclosed primary and motor feeder are outside the test board.
Digital multimeter
Control disconnect closed · Unlocked · Secondary unverified · Coil link connected.
0 of 3 diagnostic measurements recorded.
Unit 2 service call
The pressure on the graphic disagrees with the field transmitter.
Locate the first disagreement between the field signal, controller conversion and displayed value. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
Work an AHU fan-start service call
Gather live and isolated readings, enter the diagnosis, repair the virtual circuit and prove sustained fan operation in the same work order.
Open simulator →Knowledge check
Pass at 80%. Every safety item must also pass.
Field takeaways
- Confirm zero voltage and isolate the component before interpreting ohms.
- Specify element type and curve, terminal pair and temperature in the service record.
References and further reading
- Fluke · Measuring resistance with a digital multimeter ↗
- Belimo · Resistance characteristics of passive temperature sensors ↗