What you’ll learn
- Separate electrical travel, linkage motion and process response.
- Design a stroke test that accounts for travel time and load.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.Observe both sides of the linkage
A position output usually describes the actuator's internal position. A loose coupler or slipping clamp can leave the shaft stationary while that output follows every stroke. Identify which member the A returned observation such as position or speed. Locate the pickup to see which part of the mechanism it represents. sensor actually observes. Use a local witness at the shaft and a process measurement such as downstream flow to establish delivered action.
Let the process respond
Record baseline pump state, differential pressure and coil entering temperatures. In the training plant, exercise the valve at endpoints and an intermediate position, allowing actuator travel and then thermal settling. Equal increments of valve travel seldom produce equal increments of flow. Repeat the sequence in reverse to reveal sticking and Different switching thresholds for a rising and falling signal. Between thresholds the prior state matters. .
- AO command
- Position feedback
- Coupling and valve stem
- Branch flow
- Leaving-air response
Normal operation
Example training conditions
- In a heating trial the command rises from 30% to 70%; the stem moves in the correct direction, branch flow rises from 2 to 4 gpm, and leaving air warms after a delay.
- Airflow and supply-water temperature remain comparable between samples. Those conditions make the process response interpretable.
Worked service example
A reheat coil produces little heat after an actuator replacement.
Recorded field evidence · training example
- Command 100%. Internal feedback 99%.
- Pump differential 14 psid. Branch flow 0.2 gpm.
- On the simulated full stroke the actuator moves while the stem witness mark stays still.
Travel ends at the coupling. Confirm the mechanical attachment and retest flow at comparable pump pressure.
Field procedure
- Identify normal operating position and permitted range.
- Observe actuator and stem at both ends with adequate travel time.
- Recheck branch flow and temperature rise after restoring automatic control.
Hands-on exercise
Change the actuator request and watch how feedback and delivered response behave during travel.
AHU actuator stroke and process response
Command at least 75% for ten simulated seconds and record the missing travel. Identify the fault, repair the virtual heating valve, and repeat the stroke. Compare the temperature trend before and after repair. Release the test command after the verified stroke.
HW-GPM · measured branch flow 0.0 gpm. BLR-01.DIST-T · available supply water 145.9°F.
Inspect trend samples
| Time (s) | Command (%) | Travel (%) | Flow (gpm) | DAT (°F) |
|---|---|---|---|---|
| 60 | 0.0 | 0.0 | 0.0 | 66.5 |
Unit 10 service call
A checkout point moves in the wrong direction under load.
Leave a reproducible point-to-point, functional and restoration record. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
Rooftop damper graphic
In Instructor, apply Outside blades stuck shut. Compare OAD-CMD, OAD-FB and OAD-POS while advancing the clock. Remove the fault afterward.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Witness the driven member and process response.
- A process result needs its load and pressure context.
References and further reading
- DOE FEMP · Commissioning for Federal Facilities ↗
- Caleffi idronics 32 · Troubleshooting Hydronic Systems ↗