The open office has no supply air
Air-handling unit · Electrical · Intermediate
Customer complaint
The first-floor office reports still air after occupied start. Trace the fan request through the 24 VAC control circuit, record your meter evidence, and return AHU-01 to service.
Equipment and operating sequence
On this simulated AHU, a DDC dry contact sends control voltage through a removable test link to K1. A separate K1 contact grants the drive run permission. Coil return A2 shares the X2 reference. The control disconnect and all selectable test points belong to the virtual wiring panel.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- At dispatch, occupied operation was requested and the supply fan command was ON.
- Fan run proof remained OFF after the startup interval.
- The supply airflow reading was 0 cfm.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Schneider Electric · Control relay terminal markings ↗
Coil terminal designations A1 and A2 and independent normally open relay contacts.
Fluke · 110 series multimeter manual ↗
Measurement functions for AC voltage, resistance and continuity.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Supply fan · case readings
- Occupied request Command
- On
- Supply fan command Command
- On
- Fan run proof Feedback
- Off
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Occupied request | Command · Supply fan | On | — | On | — | — | — |
| Supply fan command | Command · Supply fan | On | — | On | — | — | — |
| Fan run proof | Feedback · Supply fan | Off | — | — | Off | — | — |
| Supply airflow | Reading · Duct / zones | 0 | cfm | — | — | — | — |
Intake observations
- At dispatch, occupied operation was requested and the supply fan command was ON.
- Fan run proof remained OFF after the startup interval.
- The supply airflow reading was 0 cfm.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.