What you’ll learn
- Use local readings to distinguish sensing and network problems.
- Identify a fault boundary from neighboring devices.
Before you start · 2 related lessons
0 of 2 prerequisites demonstrated. You can open this lesson at any time.Three places can disagree
Compare a colocated reference, the field controller's local input and the supervisory object at nearly the same time. A local input that tracks the reference while the supervisor retains yesterday's value points toward transport, conversion or binding. A supervisor that mirrors a biased local input sends the investigation back toward the sensor, installation and scaling.
Use another object as a witness
Collect age, value, units and quality from a peer on the same controller, another controller on the same routed segment and one on a different segment. More than one stale object behind the same route suggests a common dependency. Verify the documented network path and the device identity before attributing the failure to the wiring or router.
- Reference instrument
- Local input and clock
- Routed object
- Supervisor sample time
Normal operation
Example training conditions
- At 13:05 the local display reads 68.1°F, the workstation reports 68.1°F with a fresh update and an independent thermometer reads 68.3°F.
- Location and sample time make these three observations comparable. A cached workstation value must carry its earlier timestamp.
Worked service example
A supervisory trend shows a constant 69°F in a warming office.
Recorded field evidence · training example
- Local reference 74.0°F. Field controller 74.2°F.
- Supervisor 69.0°F, last update 08:02. Current time 08:22.
- Neighboring points on the same device also last updated at 08:02.
The local sensor tracks the room. Determine where fresh updates cease along this device's communication path.
Field procedure
- Record clock offsets and the stated update interval.
- Compare field and supervisory values for the same identified object.
- Check the affected group and verify a new change reaches the destination after correction.
Hands-on exercise
Compare device identification and communication status at more than one station.
Compare sensor bias with a stale supervisory sample
Two example calls involve the same zone and a reported 69°F. All clocks are aligned. A traceable room reference has stabilized alongside the sensor; the site expects a new supervisory sample at least every 30 seconds.
Compare both local reference checks, then compare the stale graphic with its unaffected neighbor. Calculate the age of the stale sample.
Unit 9 service call
East wing temperatures are flat on the BAS while the equipment still responds.
Use local references, point age and affected devices to bound the fault. Bring back the source, reading and time of your strongest observation.
Open case simulatorStandalone simulator · free practice
BACnet MS/TP diagnostic clinic
Inspect a network case and document which observations distinguish a single-device problem from a shared trunk failure.
Open simulator →Knowledge check
Pass at 80%.
Field takeaways
- Compare reference, local input and point age.
- Localize the affected scope before altering configuration.
References and further reading
- BACnet Committee · Objects, Properties and Services ↗
- DOE FEMP · Commissioning for Federal Facilities ↗