Supply temperature swings despite a steady load
Air-handling unit · Sequences of operation · Advanced
Customer complaint
Supply temperature and cooling demand cycle repeatedly. Use synchronized trends to distinguish a mechanical response problem from unstable control.
Equipment and operating sequence
Illustrative chilled-water AHU at steady airflow, load, and water temperature. A validated commissioning configuration is available for comparison; all tuning changes occur only in the simulator.
For this cooling-loop test, the hot-water branch is isolated. Adjust cooling output and compare actuator travel with discharge temperature on the trend log.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Supply-air target: 55°F; measured supply air cycles between 49°F and 62°F every 3 minutes.
- Valve demand cycles between 0% and 100%; physical stem position follows smoothly with a 30-second travel time.
- Entering chilled water: 44±0.2°F; entering air: 76±0.3°F; airflow: 9,000±100 cfm.
- Sensor reference agrees; ten-second trends show valve movement precedes the temperature reversals.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Belimo: Complying with ASHRAE Guidelines for Indoor Air Quality during COVID-19, diagnostic checklist, pages 4–7 ↗
Used only for stable diagnostic checks: sensor accuracy, actuator/linkage/blade distinction, actual flow, and valve seat leakage. Dated ventilation policy recommendations are not adopted.
Trane Engineers Newsletter 50-2: ASHRAE Guideline 36, May 2021 ↗
Terminal requests and trim-and-respond pressure reset concepts; synthetic cases do not claim compliance with a current guideline edition.
ASHRAE Handbook: Fundamentals of Control, Chapter 7 ↗
PI/PID feedback, integral action, process timing and tuning principles. The numerical tuning values in AHU-08 are authored assumptions, not universal settings.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Duct / zones · case readings
- Supply-air target Setpoint
- 55 °F
- Supply-air cycle range Reading
- 49–62 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Supply-air target | Setpoint · Duct / zones | 55 | °F | — | — | — | — |
| Supply-air cycle range | Reading · Duct / zones | 49–62 | °F | — | — | — | — |
| Valve demand range | Command · Coils and valves | 0–100 | % | 0–100 | — | — | — |
| Entering chilled water | Reading · Coils and valves | 44 ± 0.2 | °F | — | — | — | — |
Intake observations
- Supply-air target: 55°F; measured supply air cycles between 49°F and 62°F every 3 minutes.
- Valve demand cycles between 0% and 100%; physical stem position follows smoothly with a 30-second travel time.
- Entering chilled water: 44±0.2°F; entering air: 76±0.3°F; airflow: 9,000±100 cfm.
- Sensor reference agrees; ten-second trends show valve movement precedes the temperature reversals.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| AHU | Supply-air target: 55°F; measured supply air cycles between 49°F and 62°F every 3 minutes. | Intake record |
| AHU | Valve demand cycles between 0% and 100%; physical stem position follows smoothly with a 30-second travel time. | Intake record |
| AHU | Sensor reference agrees; ten-second trends show valve movement precedes the temperature reversals. | Intake record |