Work order AHU-11

The open office has no supply air

Air-handling unit · Electrical · Intermediate

← Service dispatch
Isolated case simulation0/3 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

The first-floor office reports still air after occupied start. Trace the fan request through the 24 VAC control circuit, record your meter evidence, and return AHU-01 to service.

Equipment and operating sequence

On this simulated AHU, a DDC dry contact sends control voltage through a removable test link to K1. A separate K1 contact grants the drive run permission. Coil return A2 shares the X2 reference. The control disconnect and all selectable test points belong to the virtual wiring panel.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • At dispatch, occupied operation was requested and the supply fan command was ON.
  • Fan run proof remained OFF after the startup interval.
  • The supply airflow reading was 0 cfm.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Schneider Electric · Control relay terminal markings ↗
Coil terminal designations A1 and A2 and independent normally open relay contacts.

Fluke · 110 series multimeter manual ↗
Measurement functions for AC voltage, resistance and continuity.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Supply fan · case readings

Occupied request Command
On
Supply fan command Command
On
Fan run proof Feedback
Off

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Occupied requestCommand · Supply fanOn—On———
Supply fan commandCommand · Supply fanOn—On———
Fan run proofFeedback · Supply fanOff——Off——
Supply airflowReading · Duct / zones0cfm————

Intake observations

  • At dispatch, occupied operation was requested and the supply fan command was ON.
  • Fan run proof remained OFF after the startup interval.
  • The supply airflow reading was 0 cfm.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

No alarm observation is included in the evidence collected so far.

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.

Field mentor