Circulator running while startup waits for flow
Boiler · Hydronic systems · Foundation
Customer complaint
A boiler will not start although the pump appears healthy. Establish whether water is actually circulating.
Equipment and operating sequence
Illustrative boiler circuit: startup requires measured flow above its documented 20 gpm permissive. The normal operating flow is 30 gpm.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Pump command and motor-running feedback are ON for 90 seconds.
- Independent flow meter reads 7 gpm; flow permissive remains OFF.
- Boiler controller reports Waiting for Flow; burner is OFF.
- Isolation-valve position indicators show their documented operating positions.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.
Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Circulation · case readings
- Circulator Command
- On
- Pump motor running Feedback
- On
- Independent flow Reading
- 7 gpm
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Circulator | Command · Circulation | On | — | On | — | — | — |
| Pump motor running | Feedback · Circulation | On | — | — | On | — | — |
| Independent flow | Reading · Circulation | 7 | gpm | — | — | — | — |
| Burner | Status · Boiler | Off | — | — | — | Off | — |
Intake observations
- Pump command and motor-running feedback are ON for 90 seconds.
- Independent flow meter reads 7 gpm; flow permissive remains OFF.
- Boiler controller reports Waiting for Flow; burner is OFF.
- Isolation-valve position indicators show their documented operating positions.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.