One heating zone stays cold
Boiler · Hydronic systems · Foundation
Customer complaint
Other zones heat normally, but one office remains cold even with a full valve command. Identify the failed link.
Equipment and operating sequence
Illustrative two-way zone valve with actuator-position feedback. Its feedback reports actuator rotation, not actual valve-plug position or water flow.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Zone temperature is 63°F against a 70°F occupied target.
- Heating header supply is 150°F; neighboring zones heat normally.
- Zone-valve command is 100% and actuator feedback is 100%.
- Branch flow is 0 gpm; temperatures downstream of the valve remain near 70°F.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.
Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Distribution · case readings
- Zone temperature Reading
- 63 °F
- Zone target Setpoint
- 70 °F
- Zone valve Command
- 100 %
- Actuator position Feedback
- 100 %
- Branch flow Reading
- 0 gpm
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Zone temperature | Reading · Distribution | 63 | °F | — | — | — | — |
| Zone target | Setpoint · Distribution | 70 | °F | — | — | — | — |
| Zone valve | Command · Distribution | 100 | % | 100 | — | — | — |
| Actuator position | Feedback · Distribution | 100 | % | — | 100 | — | — |
| Branch flow | Reading · Distribution | 0 | gpm | — | — | — | — |
Intake observations
- Zone temperature is 63°F against a 70°F occupied target.
- Heating header supply is 150°F; neighboring zones heat normally.
- Zone-valve command is 100% and actuator feedback is 100%.
- Branch flow is 0 gpm; temperatures downstream of the valve remain near 70°F.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.