Work order BL-04

Heating water is too cool on a cold morning

Boiler · Sensors and instrumentation · Intermediate

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

The boiler follows its target, yet several rooms cannot recover. Check how that target is selected.

Equipment and operating sequence

Illustrative condensing plant reset curve: 110°F supply at 60°F outdoor air, increasing linearly to 150°F at 20°F outdoors; targets are clamped at those endpoints.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • BMS outdoor-air reading is 60°F; its quality flag is Good.
  • Calculated water target and measured system supply both read 110°F.
  • Multiple zones are below occupied setpoint with heating valves near full open.
  • No boiler lockout, capacity limit, or manual target override is active.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.

Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Boiler · case readings

BMS outdoor air Reading
60 °F · Good flag

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
BMS outdoor airReading · Boiler60°F——Good flag—
Water targetSetpoint · Supply header110°F———No manual target override
Measured system supplyReading · Supply header110°F————

Intake observations

  • BMS outdoor-air reading is 60°F; its quality flag is Good.
  • Calculated water target and measured system supply both read 110°F.
  • Multiple zones are below occupied setpoint with heating valves near full open.
  • No boiler lockout, capacity limit, or manual target override is active.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
BoilerNo boiler lockout, capacity limit, or manual target override is active.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

No historical series or trend observation is included in the evidence collected so far.