Work order BL-05

Burner repeatedly starts and stops

Boiler · Sequences of operation · Intermediate

← Service dispatch
Isolated case simulation0/2 tests recordedInvestigation openDraft autosaves in this browser

Customer complaint

Trend data shows many short burner cycles during steady heating demand. Identify what changed before recommending additional equipment.

Equipment and operating sequence

Illustrative on/off plant with adequate connected water volume. Approved normal control starts at 140°F and stops at 150°F; all OEM limits remain independent.

Dispatch intake record

These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.

  • Heat demand remains ON for 30 minutes.
  • Burner cycles approximately every 50 seconds, stopping near 150°F and restarting near 149°F.
  • Water flow and connected zone count match a previously stable operating period.
  • No local high-limit trip or flame-loss event appears in the event log.
Equipment and training references

Case readings are fictional. These resources document the principles used in the work order.

Caleffi idronics 32: Troubleshooting hydronic systems ↗
Sequence-based hydronic diagnosis, target temperature, flow, and heat transport.

Lochinvar Knight Fire Tube Service Manual, Rev G, models 55–399 ↗
Control inputs, outputs, local sequence, and equipment-side diagnosis. Boiler scenarios remain generic authored configurations, not a simulation of this exact model.

Equipment graphic

Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.

Boiler · case readings

Heat demand Status
On
Observed cycle period Reading
≈50 s

Point list

Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.

Point nameDescriptionPresent valueUnitsCommandedFeedbackStatusOverride
Heat demandStatus · BoilerOn———On—
Observed cycle periodReading · Boiler≈50s————
Stop temperatureReading · Supply header≈150°F————
Restart temperatureReading · Supply header≈149°F————

Intake observations

  • Heat demand remains ON for 30 minutes.
  • Burner cycles approximately every 50 seconds, stopping near 150°F and restarting near 149°F.
  • Water flow and connected zone count match a previously stable operating period.
  • No local high-limit trip or flame-loss event appears in the event log.

Alarm records

Reported condition and event observations. Priority and acknowledgment are shown only when documented.

EquipmentAlarm / event descriptionRecord sourcePriorityTimestampAcknowledgment
BoilerNo local high-limit trip or flame-loss event appears in the event log.Intake recordUnreportedUnreportedUnreported

Trend and history records

Recorded comparisons, event timing and time-series observations from this work order.

EquipmentRecorded trend evidenceRecord source
BoilerHeat demand remains ON for 30 minutes.Intake record
BoilerBurner cycles approximately every 50 seconds, stopping near 150°F and restarting near 149°F.Intake record
BoilerWater flow and connected zone count match a previously stable operating period.Intake record