Plant graphic says stopped while cooling continues
Chiller · Controls and communications · Foundation
Customer complaint
A stop indication appears on the supervisor, but building temperatures remain stable. Establish whether equipment stopped or the displayed evidence became unreliable.
Equipment and operating sequence
The chiller can continue under its local controller during a supervisory network interruption; this model retains its last valid remote setpoint.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- 11:25: supervisor shows chiller STOPPED and leaving water 47°F.
- Those points were last updated at 11:05; their quality flag is STALE.
- Local panel at 11:25 reports RUNNING, leaving water 44°F, no active trip.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Compressor · case readings
- Supervisor run indication Feedback
- Stopped · Stale
- Local run indication Feedback
- Running
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Supervisor run indication | Feedback · Compressor | Stopped | — | — | Stopped | Stale | — |
| Supervisor leaving water | Reading · Evaporator | 47 | °F | — | — | Stale | — |
| Local run indication | Feedback · Compressor | Running | — | — | Running | — | — |
| Local leaving water | Reading · Evaporator | 44 | °F | — | — | — | — |
Intake observations
- 11:25: supervisor shows chiller STOPPED and leaving water 47°F.
- Those points were last updated at 11:05; their quality flag is STALE.
- Local panel at 11:25 reports RUNNING, leaving water 44°F, no active trip.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| Chiller | Local panel at 11:25 reports RUNNING, leaving water 44°F, no active trip. | Intake record | Unreported | 11:25 | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| Chiller | 11:25: supervisor shows chiller STOPPED and leaving water 47°F. | Intake record |
| Chiller | Those points were last updated at 11:05; their quality flag is STALE. | Intake record |
| Chiller | Local panel at 11:25 reports RUNNING, leaving water 44°F, no active trip. | Intake record |