High water flow with a small plant temperature rise
Chiller · Hydronic systems · Intermediate
Customer complaint
Operators suspect that the plant needs another chiller because flow is high. Use temperature and flow evidence to distinguish cooling load from unnecessary recirculation.
Equipment and operating sequence
Illustrative variable-primary water-only plant with a modulating minimum-flow bypass. Evaporator minimum is 150 gpm; measured coil flow is 200 gpm. The pump maintains the approved distribution-pressure target and coil demand is unchanged for the recovery comparison.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- 10:30: evaporator flow 600 gpm; CHWS 44°F; mixed return 48°F.
- Coil branch flow 200 gpm; coil return 56°F; readings independently checked.
- Minimum-flow bypass command 0%; chiller load approximately 100 tons, below available capacity.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Evaporator · case readings
- Evaporator flow Reading
- 600 gpm
- CHWS Reading
- 44 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Evaporator flow | Reading · Evaporator | 600 | gpm | — | — | — | — |
| CHWS | Reading · Evaporator | 44 | °F | — | — | — | — |
| Mixed return | Reading · CHW distribution | 48 | °F | — | — | — | — |
| Bypass valve | Command · CHW distribution | 0 | % | 0 | — | — | — |
Intake observations
- 10:30: evaporator flow 600 gpm; CHWS 44°F; mixed return 48°F.
- Coil branch flow 200 gpm; coil return 56°F; readings independently checked.
- Minimum-flow bypass command 0%; chiller load approximately 100 tons, below available capacity.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
No historical series or trend observation is included in the evidence collected so far.