Lead machine is fully loaded but standby stays idle
Chiller · Sequences of operation · Intermediate
Customer complaint
The lead chiller cannot meet the sustained load, yet the available standby unit does not receive a start request. Find the blocked staging step.
Equipment and operating sequence
Two illustrative 250-ton chillers. Approved sequence stages the second after load exceeds 230 tons and CHWS exceeds 46°F continuously for five minutes; all other staging conditions are satisfied.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- 16:20: lead at 100% capacity; measured building load approximately 300 tons.
- CHWS 49°F against 44°F target; staging conditions TRUE for 12 minutes.
- Standby available TRUE; start command OFF; stage-up timer still timing.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Trane: Chilled-Water Systems, TRG-TRC016-EN ↗
Chilled-water and condenser-water circuits, load, bypass flow, and plant control relationships.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Compressor · case readings
- Lead capacity Reading
- 100 %
- Building load Reading
- ≈300 tons
- Standby start Command
- Off
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Lead capacity | Reading · Compressor | 100 | % | — | — | — | — |
| Building load | Reading · Compressor | ≈300 | tons | — | — | — | — |
| CHWS | Reading · Evaporator | 49 | °F | — | — | — | — |
| Standby start | Command · Compressor | Off | — | Off | — | — | — |
Intake observations
- 16:20: lead at 100% capacity; measured building load approximately 300 tons.
- CHWS 49°F against 44°F target; staging conditions TRUE for 12 minutes.
- Standby available TRUE; start command OFF; stage-up timer still timing.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
No alarm observation is included in the evidence collected so far.
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| Chiller | CHWS 49°F against 44°F target; staging conditions TRUE for 12 minutes. | Intake record |