Cooling weakens on a mild afternoon
Refrigeration system · Refrigeration · Intermediate
Customer complaint
Determine what changed in condenser heat rejection before selecting a refrigerant-side repair.
Equipment and operating sequence
Air-cooled R-134a TXV cooler. Stable snapshots have comparable box load and 80°F condenser-entering air; no low-ambient head-pressure mode is active.
Dispatch intake record
These readings were recorded when the complaint was filed. The equipment views show the running training model under the same fault.
- Box: 43°F against 35°F target; continuous cooling demand.
- Condensing saturation temperature: 130°F versus 105°F in the matched normal snapshot.
- Both condenser fans are commanded on; no fresh high-pressure trip is shown.
- Condenser-entering air: 80°F at the coil; discharge-air temperature is elevated.
Equipment and training references
Case readings are fictional. These resources document the principles used in the work order.
Danfoss: Troubleshoot common cold room faults ↗
Airflow, defrost, load, refrigerant-feed checks, and separating possible causes with additional evidence.
Heatcraft H-IM-CU Installation and Operations Manual, September 2026, version 011 ↗
Pages 29–35: pumpdown and defrost sequences, measurement locations, and competing refrigeration fault causes. Authored R-134a teaching cases do not imply this manual approves a specific new installation or refrigerant.
Equipment graphic
Case intake snapshot · Select a component group to inspect its reported values. Symbols identify equipment groups in this case family.
Evaporator / box · case readings
- Box temperature Reading
- 43 °F
Point list
Read-only intake values. Priority-array tests add documented overrides. A dash means no value was supplied for that column.
| Point name | Description | Present value | Units | Commanded | Feedback | Status | Override |
|---|---|---|---|---|---|---|---|
| Box temperature | Reading · Evaporator / box | 43 | °F | — | — | — | — |
| Condensing saturation | Reading · Condenser | 130 | °F | — | — | — | — |
| Condenser fans | Command · Condenser | On | — | On | — | — | — |
| Condenser entering air | Reading · Condenser | 80 | °F | — | — | — | — |
Intake observations
- Box: 43°F against 35°F target; continuous cooling demand.
- Condensing saturation temperature: 130°F versus 105°F in the matched normal snapshot.
- Both condenser fans are commanded on; no fresh high-pressure trip is shown.
- Condenser-entering air: 80°F at the coil; discharge-air temperature is elevated.
Alarm records
Reported condition and event observations. Priority and acknowledgment are shown only when documented.
| Equipment | Alarm / event description | Record source | Priority | Timestamp | Acknowledgment |
|---|---|---|---|---|---|
| Refrigeration | Both condenser fans are commanded on; no fresh high-pressure trip is shown. | Intake record | Unreported | Unreported | Unreported |
Trend and history records
Recorded comparisons, event timing and time-series observations from this work order.
| Equipment | Recorded trend evidence | Record source |
|---|---|---|
| Refrigeration | Condensing saturation temperature: 130°F versus 105°F in the matched normal snapshot. | Intake record |