Lesson · 12 min
Point types, signals, and physical proof
Identify what a point represents, scale its signal, and separate a command from equipment response.
Start with the point's job
An analog input represents a changing quantity, such as temperature. A binary input represents a state, such as a proving contact. Analog outputs request modulation; binary outputs request a state. A calculated demand or setpoint can exist entirely in software. Confirm the point list and controller documentation before assuming that a graphic corresponds to a particular terminal.
- AI: measured value. BI: reported state.
- AO: modulating request. BO: switching request.
- A software point may have no dedicated physical I/O.
Match the signal and sensor curve
Voltage, current, and passive resistance are different signal types. For passive temperature sensors, both the element and its curve matter: Belimo publishes separate NTC10k2, NTC10k3, NTC20k, platinum, and nickel characteristics. Two sensors described as 10 kΩ can follow different curves away from their nominal temperature. Check the exact part and configured input type before applying a calibration offset.
Scale the electrical span
For a linear example, fraction = (signal − lower signal) ÷ (upper signal − lower signal). On a configured 2–10 V span, 6 V represents 50%; on a 0–10 V span, it represents 60%. This is signal scaling, not proof of airflow or heat output. Controller configuration must also map that span to the correct engineering range and units.
Follow the evidence through the device
Trace command → electrical signal → actuator movement → process response. A position feedback value adds evidence about the actuator, while airflow or temperature adds evidence about the process. Belimo's LF24-SR US is one example with a 2–10 V application; its documented current conversion is specific to that product and configuration. Use the installed device's manual for actual wiring and tests.
TRY THE ARITHMETIC
Signal scaling
Use one consistent signal unit. A percentage represents a scaled signal; it does not establish flow or mechanical travel.
(signal − low) / (high − low) × 10050.0%Teaching example. No connection to equipment.Field exercise
Fictional exercise: an outdoor damper is commanded to 50%. What does the evidence establish?