Lesson · 12 min

Point types, signals, and physical proof

Identify what a point represents, scale its signal, and separate a command from equipment response.

Start with the point's job

An analog input represents a changing quantity, such as temperature. A binary input represents a state, such as a proving contact. Analog outputs request modulation; binary outputs request a state. A calculated demand or setpoint can exist entirely in software. Confirm the point list and controller documentation before assuming that a graphic corresponds to a particular terminal.

  • AI: measured value. BI: reported state.
  • AO: modulating request. BO: switching request.
  • A software point may have no dedicated physical I/O.

Match the signal and sensor curve

Voltage, current, and passive resistance are different signal types. For passive temperature sensors, both the element and its curve matter: Belimo publishes separate NTC10k2, NTC10k3, NTC20k, platinum, and nickel characteristics. Two sensors described as 10 kΩ can follow different curves away from their nominal temperature. Check the exact part and configured input type before applying a calibration offset.

Scale the electrical span

For a linear example, fraction = (signal − lower signal) ÷ (upper signal − lower signal). On a configured 2–10 V span, 6 V represents 50%; on a 0–10 V span, it represents 60%. This is signal scaling, not proof of airflow or heat output. Controller configuration must also map that span to the correct engineering range and units.

Follow the evidence through the device

Trace command → electrical signal → actuator movement → process response. A position feedback value adds evidence about the actuator, while airflow or temperature adds evidence about the process. Belimo's LF24-SR US is one example with a 2–10 V application; its documented current conversion is specific to that product and configuration. Use the installed device's manual for actual wiring and tests.

TRY THE ARITHMETIC

Signal scaling

Use one consistent signal unit. A percentage represents a scaled signal; it does not establish flow or mechanical travel.

LINEAR SIGNAL MAP50.0% of span
WIRE SIGNAL6
210
ENGINEERING RANGE50.0%
0%100%
The same position maps the signal to the configured engineering range. Scaling alone does not prove calibration or physical response.
(signal − low) / (high − low) × 10050.0%Teaching example. No connection to equipment.

Field exercise

Fictional exercise: an outdoor damper is commanded to 50%. What does the evidence establish?

The documented command span is 2–10 V.A qualified technician records 6 V at the applicable signal reference.The damper linkage and actual outdoor airflow have not been inspected.
Select the best supported next step

Knowledge check

Answer all four questions. Pass the field exercise and at least three questions to complete this lesson.

1Which example most clearly represents a binary input?
2What fraction does 12 mA represent on a linear 4–20 mA span?
3Two 10 kΩ sensors disagree away from their nominal temperature. What should be checked first?
4Which observation best adds evidence of useful damper operation?
0/4 answered

Sources and scope

These original exercises draw on the sources below. For equipment settings and field actions, use the exact model, firmware, approved sequence and site procedure. Sources reviewed October 20, 2026.