Control and verification

PID tuning reference

Interpret a loop trend using target, process value, output, output limits and the physical response.

Symptoms and the first comparison

Symptoms and the first comparison
Trend patternField check
Output goes up while the error growsVerify intended control direction, actuator orientation and the sensor used by the block. A heating and cooling process respond with opposite signs.
Output is limited and the error persistsConfirm load, available heating/cooling, flow, actuator travel and programmed limits. Additional gain cannot exceed an output limit.
Output moves smoothly and feedback sticks then jumpsCheck valve or damper linkage, stiction and actuator stroke before changing tuning.
Process and output cycle with repeatable lagHold a repeatable load. Compare delay, stroke time, proportional settings and integral timing. Check for a moving reset target or a second competing loop.
Large output spikes from tiny input changesLook for noisy feedback, derivative sensitivity, sampling interval or poor sensor placement.
Automatic control jumps after release from manualInspect integral tracking, output initialization, active priorities and the controller’s documented handoff behavior.

Field example

A valve stays at 100% while verified discharge temperature is 8°F above cooling setpoint. Check chilled-water flow and temperature before increasing proportional gain.

Procedure

  1. Record the active setpoint, measured variable, output, units, limits, operating mode and starting parameters.
  2. Predict the process direction. Apply one repeatable disturbance in the simulator.
  3. Compare overshoot, settling, persistent offset and equipment cycling. Preserve the prior configuration and document any accepted change.