What you’ll learn

  • Distinguish a static-pressure request from a colder supply-air request.
  • Explain how bounded trim-and-respond logic reacts to persistent demand.
Before you start · 2 related lessons0 of 2 prerequisites demonstrated. You can open this lesson at any time.

Choose the sequence for this installation

ASHRAE Guideline 36-2024 describes high-performance HVAC operating sequences and functional tests. The worked reset here uses a fictional training configuration. Check the edition, addenda, equipment configuration and limits adopted for the project before interpreting requests or changing a target. The earlier published addendum in the references illustrates how a reset request is defined.

One system has two different jobs

A static pressure reset adjusts the duct pressure target that the fan-speed loop maintains. A supply-air temperature reset changes the discharge target that the cooling or heating loop maintains. If a box is open and actual airflow falls below target, more available pressure may help. If the box already receives its design airflow but its zone remains hot, investigate supply temperature and zone load before increasing fan pressure.

Work a bounded reset through two evaluation intervals

A training sequence holds static pressure between 0.60 and 1.40 in. w.c. At each evaluation it trims 0.05 when all valid zones are satisfied. For a persistent unmet zone it responds by adding 0.10. Starting at 0.64, one satisfied interval reaches the lower limit of 0.60. A later qualifying request moves the target to 0.70. The inner fan-speed loop must still build duct pressure. Check the request signal, active target, measured pressure and delivered terminal flow in that order. The steps and limits here are illustrative.

Ask the requesting zone to prove its case

Trend damper , measured blade or actuator position, actual and target airflow and the zone error. A closed fire damper, crushed branch or biased airflow pickup can create a persistent requester. Raising the building-wide pressure to serve a defective branch adds fan power and can increase noise elsewhere. Evaluate the common supply and at least one neighboring branch at similar load.

Give interacting loops time to respond

Trim-and-respond logic reduces a gradually when few requests persist, then increases it within bounds as credible requests accumulate. Supply temperature also affects how much air terminals need. Warmer supply can reduce reheat at light loads while requiring more airflow for cooling and reducing dehumidification. Evaluate fan energy, representative zone conditions and humidity together over comparable occupied hours.

Pressure reset feedback
  1. Terminal flow shortfall and damper state
  2. Qualified zone request
  3. Bounded static target change
  4. Fan-speed response
  5. New measured terminal flow

Normal operation

Example training conditions

  • Under light load, several terminals hold their airflow close to target with dampers partly open. Under the example reset sequence, no persistent increase requests arrive and the duct-pressure target trims downward within its limits.
  • Recheck delivered airflow after the target moves. The allowed limits and request rules belong to the project sequence.

Worked service example

One box sends continuous pressure requests while other served zones are quiet.

Recorded field evidence · training example

  • VAV-7 damper feedback 98%, target 800 cfm, measured 390 cfm
  • Adjacent box meets 750 cfm at 55% damper
  • Duct pressure at the main sensor tracks its existing target

The main loop is achieving its commanded pressure. Compare branch inlet pressure and independently validate VAV-7 flow before allowing that zone to drive an aggressive system reset.

Field procedure

  1. Compare the sensed duct pressure and target over the request period.
  2. Identify which zone repeatedly requests and whether it measures a genuine unmet load.
  3. Check reset bounds and response intervals, then compare conditions before and after any approved adjustment.

Hands-on exercise

Compare ideal fan power at two fan speeds. Use the result to explain the cost of maintaining excess static at light load.

VFD and fan affinity laws

At full speed this fan delivers 6,000 cfm at 1.8 in. w.c. and 5 kW of shaft power. The illustration holds wheel diameter, air density and the system resistance curve constant.

0% speed100% speed
Airflow %Pressure %Shaft power %
6000 cfm · 1.80 in. w.c. · 5.000 kW shaft power

Reduce speed to 50%. Calculate shaft power as a percentage of its full-speed value.

Unit 6 service call

The heating valve is at 100%. Why is the discharge air still cold?

Trace load, air and heat from the unit to the occupied zone and verify automatic recovery. Bring back the source, reading and time of your strongest observation.

Open case simulator

Knowledge check

Pass at 80%.

1. A training reset target is 1.36 in. w.c., with an upper limit of 1.40. A qualified request adds 0.10. What target reaches the inner fan loop?
2. Seven boxes meet airflow target. One box has a leaking pickup tube and falsely reports low flow for hours. Which response best protects the reset sequence?
3. A terminal meets design airflow but the space remains warm. Which evidence most directly distinguishes an overly warm primary supply from inadequate flow?
4. A fictional static reset trims 0.03 in. w.c. per eligible interval. Starting at 1.20, what target follows three no-request intervals if no limits intervene?
5. Under ideal fan affinity assumptions, what percentage of original shaft power is required at 80% speed?

Field takeaways

  • Reset the target associated with the observed shortfall.
  • Persistent requests deserve a field comparison before the entire system responds.