Level 1 · Applied HVAC physics

Measure pressure difference and flow

14 minutes · Foundation

Reading open · Practical open · Knowledge check open

What you’ll learn

  • Calculate a pressure difference from two taps.
  • Calculate duct airflow from average velocity and area.
Before you start · 1 related lesson0 of 1 prerequisites demonstrated. You can open this lesson at any time.

Two locations make a difference

Pressure is force per unit area. is pressure at one location minus pressure at another. A fan or pump can raise the fluid pressure. Flow usually spends that pressure rise overcoming resistance through filters, pipes and fittings. Record the order and location of both taps.

Flow needs its own evidence

Flow is volume passing per unit time. For a duct, average air velocity in feet per minute times clear area in square feet gives cubic feet per minute (). One centerline reading can be faster than the average. A properly placed flow meter serves a similar purpose on a water pipe. U.S. gallons per minute is abbreviated gpm.

Changing the load

At comparable air density, raising airflow across the same filter typically increases its pressure drop. A higher drop can also indicate added resistance. Compare with a known baseline at similar flow. A shut valve can support pressure with almost no flow.

Air moving through a filter and measurement section
  1. Upstream tap
  2. Downstream tap
  3. Duct traverse

Normal operation

Example training conditions

  • At a measured 1,000 cfm, the pressure ahead of a clean filter is 0.85 inches of water column and after it 0.65. Drop is 0.20 inches.
  • A clear duct area of 2 square feet and mean velocity 500 feet per minute independently give 1,000 cfm.

Worked service example

Filter drop is higher than yesterday.

Recorded field evidence · training example

  • Yesterday measured drop 0.20 inches at 1,000 cfm.
  • Today measured drop 0.35 inches at 1,350 cfm.
  • Taps and instruments are in the same locations.

Flow increased, so a higher drop alone cannot establish a dirty filter. Compare at the previous flow or use the documented filter curve. Check the measured airflow before recommending a change.

Terms in this lesson
Differential pressure
The pressure difference between two named measurement points.
CFM
Cubic feet per minute, a rate of air delivery.

Hands-on exercise

Inspect the same filter at equal measured flow on two service visits.

Predict before inspection

How would extra filter resistance usually affect pressure drop at unchanged flow?

Virtual bench checkout

Verify your finding in the recorded case to open the bench.

Knowledge check

Pass at 80%.

1. Which pair allows a fair comparison of filter restriction over time?
2. Both sides of a closed valve show different pressures. What is established?
3. Pump discharge 22 psi and suction 16 psi at equal elevation. Find the pressure rise.
4. Average velocity 420 ft/min and clear duct area 3 ft². Find airflow.
5. Which unit describes a water flow rate?

Field takeaways

  • Name the two pressure locations and independently establish flow.

References and further reading

Technician handbook