What you’ll learn
- Predict which loads stop after a wire opens.
- Calculate a resistive series current and interpret a voltage drop.
Before you start · 1 related lesson
0 of 1 prerequisites demonstrated. You can open this lesson at any time.One path or several
In a series circuit, the same current passes through each component in one path. An open wire interrupts the whole series path. For resistors in series, add the resistances. Two 60 Ω resistors in series on 12 V DC present 120 Ω in total, draw 0.10 A, and each drops 6 V.
Branches share two endpoints
Parallel branches connect across the same two nodes. Each sees the same voltage in an ideal circuit. Opening one branch can leave the others powered. A short is an unintended low-resistance path. It can create a high current limited by the source, wiring and protection. A control switch opening the intended path is a normal switching action.
Use the return path
When reading a schematic, trace all the way from source to return. An open series contact may show almost the entire supply voltage across it when the downstream load supplies a return. Without that return, the same inference does not follow.
- Common source
- Branch A
- Branch B
Normal operation
Example training conditions
- Two equal lamps in separate parallel branches of an ideal 24 V source each have 24 V across them.
- With only branch A opened, B remains on and the total source current decreases.
Worked service example
Two devices share a control supply. Only the indicator is dark.
Recorded field evidence · training example
- Relay on branch B operates.
- Source measures 24 V across its terminals. Branch A has an open switch in series with the indicator.
Power is available to the shared source and B. The open switch interrupts A, so the dark lamp alone cannot identify a failed bulb. Check the intended switch state and the voltage directly across the lamp in the virtual circuit.
Terms in this lesson
- Node
- A set of connected points at effectively the same potential in the circuit model.
- Open circuit
- An interruption in the current path.
- Short circuit
- An unintended low-resistance connection.
Hands-on exercise
Inspect the branch paths of two loads on a single DC supply.
Predict before inspection
Virtual bench checkout
Verify your finding in the recorded case to open the bench.
Standalone simulator · free practice
Open the virtual wiring and meter laboratory
Use the board diagram and modeled test jacks. Follow the source isolation and verification sequence before an isolated resistance reading.
Open simulator →Knowledge check
Pass at 80%. Every safety item must also pass.
Field takeaways
- Trace both ends of every branch before assigning a common failure.
References and further reading
- OpenStax Physics · Electrical quantities and circuit equations ↗
- OpenStax University Physics · Electrical measuring instruments ↗
- OSHA · Electrical safety-related work practices, 29 CFR 1910.333 ↗