Original module 01 assessment

Building Automation Fundamentals

Follow a comfort complaint from the workstation through a field controller to the air delivered at the diffuser.

Module examination

Pass at 80%.

1. An AHU uses a local pressure loop and receives its occupied mode from the supervisor. What determines operation during a network outage?
2. A cooling loop holds its indicated discharge temperature at 58°F. Its sensor consistently reads 3°F above the air temperature. Estimate the actual temperature.
3. A new points list calls a discharge temperature setpoint an AI. Which document detail would establish its true origin?
4. A space heating loop uses error = setpoint minus measured temperature. Its setpoint is 72°F and its measured temperature is 67.5°F. Calculate the error.
5. Only one AHU freezes on the workstation. Its controller shows changing values and the drive is running. Which check best narrows the fault?
6. Which observation best establishes that air reached a particular supply branch?
7. The supervisor lost its connection at 08:02. At 08:07 the field controller still changes valve output with discharge temperature. Which conclusion is supported?
8. A position-servo damper holds 40% on a fixed schedule. Which statement applies to outdoor airflow?